Page 194 - Water Standards
P. 194

draulic turbine floor, generator piers and generator floor
                                can be constructed in sequence. The dimensions of the
                                second stage concrete reserved in the hydraulic turbine
                                floor shall be ensured to satisfy the enough space for stay
                                ring installation.
                             4) Conical pipe interior steel lining, runner chambers and
                                embedded parts of the stay ring should be installed at a
                                single time, for the convenience of precise control of the
                                whole installation. And the second stage concrete should
                                also be poured at a single time.
                             5) For places where the second stage concrete cannot be well
                                combined with the first stage concrete, cement grouting for
                                joint surfaces shall be carried out when the second stage
                                concrete reaches the design strength. And during grouting,
                                lifting of the embedded parts caused by grouting pressure
                                shall be avoided.
                             6) For the second stage concrete at narrow sections or places
                                that are not easily reached, the method of pre⁃packed ag⁃
                                gregate grouting concrete can be adopted for construction,
                                and this method shall meet the requirements in Article
                                2   7   30 of this specification.
                       3   9   9  All projects with wooden structures, steel structures, mason⁃
                       ry, building floors, roofs and decoration, etc. for which there are no
                       special requirements shall comply with the requirements in the current
                       relevant national standards.










                                                                            1 8 7
   189   190   191   192   193   194   195   196   197   198   199